FieldServer FS-8700-47 Computer Drive User Manual


 
FS-8700-47 DNP 3.0 Driver Manual Page 9 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8, R1-R2
1
Baud* Specify baud rate
110 – 115200, standard
baud rates only
Parity* Specify parity
Even, Odd, None, Mark,
Space
Data_Bits*
Specify data bits
7, 8
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used DNP
Handshaking*
Specify hardware handshaking
None
Poll Delay*
Time between internal polls
0-32000 seconds, 1
second.
Application*
Versions of the driver prior to 1.02a used a different
method to calculate DA offset. Refer to Appendix A.16.
It is also possible to use this parameter to control if link
resets are used/required. Refer to Appendix A.15.
OriginalStyle,
NoLink,
OrigStyle-NoLink
Example
// Client Side Connections
Connections
Port ,Baud
,Parity
,Protocol ,Handshaking
,Poll_Delay
R1 ,9600 ,None ,DNP ,None ,0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID
DNP 3.0 station address of physical Server
node
0-65535
Protocol Specify protocol used DNP
Port
Specify which port the device is connected to
the FieldServer
P1-P8, R1-R21
Example
// Client Side Nodes
Nodes
Node_Name
,Node_ID
,Protocol
,Port
PLC 1 ,1 ,DNP ,P1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.