FieldServer FS-RA-CLX-BAS Server User Manual


 
FS-RA-CLX_SlotServer_Instruction_Manual_(T17011) Page 29 of 34
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com
Appendix A.5.5. Testing
The SlotServer should now be visible to the CPU. Go Online with RSLogix and check
the Input buffer of the SlotServer for data. A good check is to examine offset 2 of the
input tag for a non-Zero value. If the SlotServer is multiplexing (DA_Count >1), then this
value will be cycling through the Buffer numbers, otherwise if DA_Count=1, then offset 2
will be fixed at 1. If offset 2 is zero, then the SlotServer is not being seen by the CPU,
and Diagnostics will need to be performed using RSNetWorx and RSLogix to determine
the cause of the problem.