FieldServer FS-RA-CLX-BAS Server User Manual


 
FS-RA-CLX_SlotServer_Instruction_Manual_(T17011) Page 9 of 34
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldServer.com
TP/FT10 LonWorks connection
This two wire connection is polarity insensitive and can be multi-dropped into a LonWorks
Network.
Ethernet Port
The Ethernet port can be used for configuration and troubleshooting, as well as for Protocols
that require an Ethernet connection. Use standard Ethernet cables for this connection.
RS-485 Port
This is a standard 2-wire RS-485 port. Specify as R1 in the configuration.
4.2. Inside Cover Door Label
A label has been provided on the inside of the cover door for the User to document
important or useful configuration parameters used. In particular, special provision has been
made to document the Ethernet port IP parameters, as well as the LonWorks DSN
(Domain/Subnet/Node) allocated by the Network Manager. These fields are there to be
utilized at the User’s discretion.
4.3. Technical Specifications
Slot width 1
BackPlane Current Load 0.6A
Operating Temperature 0-60 Deg C (32-140 Deg F)
Storage Temperature -40 – 85 Deg C (-40 – 185 Deg F)
Humidity 5-95% (Non-Condensing)
Allen Bradley Platform: ControlLogix 1756 Rack
LonWorks Connection type: TP/FT-10
Ethernet port 10/100 MB/sec.
RS-485 port 2-wire, half duplex.
Approvals
1
UL 60950-1:2003
CAN/CSA-C22.2 No.60950-1-03
1
Refer to Error! Reference source not found. to view Certificates.