Fujitsu DX90 S2 Computer Drive User Manual


 
Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
25
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.8 Power distribution unit (AC200-240V, 1U, Max 2 enclosures connection) and provided AC cable
specifications
Power distribution unit for DX80 S2/DX90 S2 (AC200-240V, 2U, Max 6 enclosures
connection)
There are 12 outlets.
Figure 1.24 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that are provided.
Table 1.9 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection) and provided AC cable
specifications
Item Specifications
Power Voltage AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Input cable Connection type IEC60320-C13 NEMA L6-15P
Length 4m
Quantity 2
Output cable Connection type IEC60320-C13 IEC60320-C14
Length 3m
Quantity 4
Item Specifications
Power Voltage AC200 - 240V
Phase Single
Frequency 50Hz/60Hz
Input cable Connection type Straight-through NEMA L6-20P
Length 4m
Quantity 2
Output cable Connection type IEC60320-C13 IEC60320-C14
Length 3m
Quantity 12
Outlets (OUTPUT)