Fujitsu DX90 S2 Computer Drive User Manual


 
Chapter 2 ETERNUS DX Disk Storage System Installation
2.1 Installation Specifications
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED P3AM-4822-12ENZ0
29
2.1.2 ETERNUS DX90 S2
The following table shows the specifications of the ETERNUS DX90 S2.
Table 2.2 ETERNUS DX90 S2 installation specifications
Item
ETERNUS DX90 S2
2.5" drive configuration 3.5" drive configuration
Dimensions
(W × D × H)
Controller enclosure 482 × 645 × 88mm (2U) 482 × 670 × 88mm (2U)
Drive enclosure 482 × 540 × 88mm (2U) 482 × 555 × 88mm (2U)
Power
distribution unit
1U 435 × 148 × 38mm
2U (485 × 280 × 43mm) × 2 (*1)
Maximum
weight (*2)
Controller enclosure 35kg
Drive enclosure 35kg
Power
distribution unit
1U 2kg
2U (6kg) × 2 (*1)
Service area Front: 800mm, Rear: 800mm
Power
Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
Number of power supply units 2 (for each enclosure)
Plug type
EMEA&I region
For AC200V connections:
IEC60320-C14G (supplied as standard)
Regions other
than EMEA&I
For AC200V connections:
NEMA L6-15P (supplied as standard)
For AC100V/AC200V connections:
IEC60320-C14 (optional)
Maximum power
requirements
(*2)
Controller
enclosure
AC 100 – 120V 630W (640VA) 620W (630VA)
AC 200 – 240V 630W (640VA) 610W (620VA)
Drive
enclosure
AC 100 – 120V 570W (580VA) 550W (560VA)
AC 200 – 240V 570W (580VA) 550W (560VA)
Maximum heat
generation (*2)
Controller
enclosure
AC 100 – 120V 2300kJ/h 2300kJ/h
AC 200 – 240V 2300kJ/h 2200kJ/h
Drive
enclosure
AC 100 – 120V 2100kJ/h 2000kJ/h
AC 200 – 240V 2100kJ/h 2000kJ/h
Maximum
amount of
exhaust air
Controller enclosure
4.0m
3
/min
Drive enclosure
4.0m
3
/min