RX600 S5 Operating Manual 57
Hardware installation Connecting the server to the mains
AC source related power supply configuration and system load limits
The system configuration and load is limited by the number of AC mains power
sources available as indicated in the following table.
Installation in PRIMECENTER/Datacenter rack
Please follow the installation requirements for connection to the mains
described in the rack manuals.
Number
of power
supply
modules
installed
AC redundant systems
(requires 2 AC sources)
AC non-redundant systems
(connected to 1 AC source)
Max. DC
loading to
support AC
redundancy
Installation
requirements
Max. DC
loading for AC
non-redundant
systems
Installation
requirements
2 830W 2 PSUs
connected to
mains (1+1)
1580W 2 PSUs
connected to
mains (1+1)
3 N/A N/A 2320W 3 PSUs
connected to
mains (2+1)
4 1580W 2 PSUs
connected to
mains
2 PSUs
connected to
an isolated AC
source
e.g. UPS (2+2)
2320W 4 PSUs
connected to
mains (3+1)
Table 4: System power supply configuration and system load limits