2.2.10 UPS command group
The UPS command group allows monitoring and configuration of the managed UPS system.
Command Parameters Description
upsinfo (*) Show detailed UPS information
upstest (*) Start/Stop UPS tests
upscontrol (*) Control the UPS (1-ph/SP versions ONLY)
upsconfig (*) Configure UPS parameters
attacheddevice [device]
Set UPS attached device
[device] Device which is powered/protected by the UPS
NOTE: Maximum length 63 chars. If this parameter contain
blanks or special characters it shall be specified in between
double quotation marks (“...”)
alarmdelay [time]
Set alarm delay time (1-ph/SP version ONLY)
[time] Time in seconds before alarm notification
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrydelay [time]
Set retry delay time (1-ph/SP version ONLY)
[time] Time in seconds between re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
retrycount [count]
Set retry count (1-ph/SP version ONLY)
[count] Number of re-connection attempts
NOTE: This parameters is factory set to its ideal value and
shall not be changed unless instructed to do so
serialbypass on | off
Enable/disable the serialbypass functionality
NOTE: This command is offered for UPS service access ONLY.
It use outside of this scope is not recommended (enabling
this functionality stops the UPS monitoring
Show/Set card address on the IMV bus
[address] Card address in the range 0, 54-57
NOTE: This setting may overrides the HW setting through the
dip-switches on the card. Setting this parameter to 0 reverts
to the HW settings.
This setting becomes active only after reboot (save the
settings!)
[address] cardaddress
Enable/disable write commands to the UPS
Setting readonlymode to on will stop any write operation
towards the UPS (the SNMP/Web adapter will effectively
switch to read-only mode). The UPS Test, Control and Config
web pages will not be shown in the navigator bar.
[on | off] readonlymode
Caution! Once enabled, this setting may not be reverted.
NOTE: 1-ph/SP versions ONLY