4.3 GE MIB OBJECTS
GE provides private MIBs, which enhance the UPS information available over SNMP interface.
These MIBs are only supported on 3-ph SNMP/Web plug-in adapter.
Two different version of the GE private MIB exist:
• GE Single MIB
: to be used for monitoring of a 3-ph UPS is single unit configuration
• GE Parallel MIB
: to be used for monitoring of a 3-ph parallel UPS system
The MIB structure is shown in the following picture. The geGenericUPS group provides information on
the unit in stand-alone configuration or on the overall system in a parallel configuration. The geFirstUPS
… geEightUPS groups provide information on the units that are part of a parallel configuration.
For each of these groups the 3-ph SNMP/Web plug-in adapter supports the following objects.
(Objects marked with [*] do not have a RFC1628 correspondence)
OIDs TRAPS & ALARMS
==== upsIdent Group ====
upsIdentManufacturer
upsIdentModel
upsIdentUPSSoftwareVersion
upsIdentAgentSoftwareVersion
upsIdentName
upsIdentAttachedDevices
upsIdentsUPSSerialNumber [*]
upsIdentComProtVersion [*]
upsIdentOperatingTime [*]
==== uspBattery Group ====
upsBatteryStatus
upsSecondsOnBattery
upsEstimatedMinutesRemaining
upsEstimatedChargeRemaining
upsBatteryVoltage
upsBatteryCurrent
upsBatteryTemperature
upsBatteryRipple [*]
==== upsInput Group ====
upsInputLineBads
upsInputNumLines
upsInputFrequency
==== geUPSTraps & upsWellKnownAlarms group
====
upsAlarmBatteryBad
upsAlarmOnBattery
upsAlarmLowBattery
upsAlarmDepletedBattery
upsAlarmTempBad
upsAlarmInputBad
upsAlarmOutputBad
upsAlarmOutputOverload
upsAlarmOnBypass
upsAlarmBypassBad
upsAlarmOutputOffAsRequested
upsAlarmUpsOffAsRequested
upsAlarmChargerFailed
upsAlarmUpsOutputOff
upsAlarmUpsSystemOff
upsAlarmFanFailure
geUPS (1.3.6.1.4.1.818.1.1)
geGenericUPS(10)
geFirstUPS(11)
geSecondUPS(12)
…
geEigthUPS(18)
Parallel
system
only
geUPS (1.3.6.1.4.1.818.1.1)
geGenericUPS(10)
geFirstUPS(11)
geSecondUPS(12)
…
geEigthUPS(18)
Parallel
system
only
upsAlarmFuseFailure
upsAlarmGeneralFault
upsAlarmDiagnosticTestFailed
upsAlarmCommunicationsLost
upsAlarmAwaitingPower
upsAlarmShutdownPending
upsAlarmShutdownImminent
Modifications reserved Page 37/58
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc Operating Manual SNMP/Web Adapter