GE GFK-2193A Network Card User Manual


 
GFK-2193A 3-1
Configuration
These configuration procedures are intended for users with at least a basic knowledge of
the CIMPLICITY Machine Edition Logic Developer software and the Series 90-30 PLC.
For help with using the software, please see the software’s built-in help system.
Note: The PROFIBUS Slave is supported only in Machine Edition Logic Developer-PLC.
Adding a PROFIBUS Slave Module to the Hardware Configuration
Add the IC693PBS201 module to the PLC rack configuration.
1. In the
Project tab of the Navigator, expand the Hardware Configuration
folder.
2. In the Hardware Configuration folder, right click the PLC Slot where you wish to install
the PROFIBUS Slave module. Note that a PROFIBUS module is not a valid choice for
slot 1 of a modular CPU rack.
3. Select Add Module from the shortcut menu. The Module Catalog dialog box appears.
Note: To edit a module that already appears in the rack, right click the module and
select Configure. The module’s Parameter Editor window opens.
4. Click the Communications tab. The Communications module list appears.
5. Select the IC693PBS201 PROFIBUS Slave and click the OK button. The module is
added to the PLC configuration in the Navigator window, and the module’s Parameter
Editor window appears in the InfoViewer window space.