GE GFK-2193A Network Card User Manual


 
1-2 Series 90™-30 PROFIBUS Slave Module User's Manual – August 2004 GFK-2121A
1
SYS
COM
PROFIBUS DP
SLAVE
5-IGND
SERVICE RS232
PROFIBUS
3-TxD
2-RxD
5-IGND
8-A
3-B
1-SHLD
1
3
2
IC693PBS201
PROFIBUS
Slave Module
4
Key
1
LEDs
System (SYS) and Communications (COM)
indicators
2
Service Port
RS232, 9-pin male, D-Shell Connector. Used
for module firmware upgrades.
3
PROFIBUS
Port
9-pin female D-Shell Connector. Used for
connecting to a PROFIBUS network.
4
Label (not
shown)
Label on side of module contains catalog
number, description, standard conformance,
and serial number information
Figure 1-1. PROFIBUS Slave Module
IC693PBS201 Slave Module Specifications
Catalog number IC693PBS201
Description Series 90-30 Slave module for PROFIBUS DP networks
Configuration software
requirement
Requires Proficy Machine Edition Logic Developer version 2.6 or later
CPU version
requirement
Requires CPU firmware version 8.00 or later
Mounting location Can reside in any Series 90-30 baseplate (CPU, expansion, or remote)
slot except for slot 1 of a modular CPU baseplate
Environment
Storage temperature = –40°C to 85°C
Operating temperature = 0°C to 60°C
Backplane current
consumption
450 mA at 5VDC (typical)
Data rates Supports all standard Data Rates (9.6KBps, 19.2KBps, 93.75KBps,
187.5KBps, 500KBps, 1.5Mbps, 3MBps, 6MBps and 12MBps)
Status information Slave Status Word
Firmware module revision
Note: The PROFIBUS Slave module does not support Sync and Freeze modes