GFK-2193A Chapter 4 Status and Diagnostics 4-11
4
(Word 9) Local PLC - Memory Starting Address: Word 9 determines the starting
address in the local PLC in which the response is to be written. The value entered is the
offset (0-based) from the beginning of PLC memory for the memory type and mode
specified in Word 8. This offset will be either in bits, bytes, or words depending on the
mode specified (for example, if Word 8=16 and Word 9=2, the starting address will be
%I9). Valid ranges of values depend on the PLC’s memory ranges.
(Word 10) Response Memory Size: Word 10 specifies the size of the memory block for
the response. The Response Memory Size is 25 words. If the Response Memory Size is
set smaller than 25, the COMMREQ will fail with a 7 in the COMMREQ Status Word. The
user is responsible for assuring that this area is large enough to contain the requested
data without overwriting other application data
Read Module Header Reply Data Format for Slave
Word Name Description
Word 1 Command Code Echo of the Command Code that this data block is replying to
(0x0005).
Word 2
ModuleType Contains 1 if the module is a Slave and a 2 if the module is a
Master.
Word 3
PfbStatus PROFIBUS Status register, also can be read using the Get
Device Status COMMREQ. For definitions, see page 4-8.
Word 4
ModuleVersion Module firmware version.
0122h = 1.22
Word 5
ErrLanOffline Counter. LAN went offline due to errors.
Word 6
DiagConf Total confirmations.
Word 7
DiagInd Total indications.
Word 8
ErrNotOk Total not OK confirmations and indications.
Word 9
DiagSlaveUpdate Number of updates the Slave has received from the Master
Word 10
ErrSlvErr Count of Slave Configuration Errors
Word 11
ErrSlvTout Count of Slave Watchdog timeouts (update not received in time)
Word 9
ErrInvReqLen Invalid request length error counter.
Word 10
ErrFifo FIFO overflow error counter.
Word 11
ErrRxOverun Receive overrun error counter.
Word 12
ErrDblTok Double token error counter.
Word 13
ErrRespErr Response error counter.
Word 14
ErrSynErr General network error counter.
Word 15
ErrNetTout Network timeout error counter.
Word 16
ErrHsa Station higher than HAS was heard counter.
Word 17
ErrStn Duplicate station detected counter.
Word 18
ErrPasTok Unable to pass token counter.
Word 19
ErrLasBad Active station list is invalid.
Word 20
ErrInternal Internal errors.
Word 21
ErrArg Argument errors.
Word 22
ErrEventOverun A new event occurred before the last one was cleared.
Note: If the Name starts with Err the value stops at the maximum. If the Name starts
with Diag the count rolls over to zero.