IBM 5000 Computer Hardware User Manual


 
Diagnostic Messages
Function: System-Management Processor Messages (165)
Result Test Specific String
Failed System-management processor on system board.
Action: Have the system serviced.
Function: Thermal System Messages (175)
Function Test Specific String
Failed Fan #1
Note: The FAN1 LED on the system board will also be on.
Action: Replace fan 1.
If the problem persists, have the system serviced.
Failed Fan #2
Note: The FAN2 LED on the system board will also be on.
Action: Replace fan 2.
If the problem persists, have the system serviced.
Failed Temperature sensed on system board is out of range.
Action: If one of the FAN LEDs on the system board is on, replace the indicated
fan.
If the problem persists, have the system serviced.
Function: Status Display Messages (180)
Result Test Specific String
Failed Information LED panel.
Action: Have the system serviced.
Failed Diagnostics LED panel.
Action: Have the system serviced.
Failed LED on system board.
Action: Have the system serviced.
Failed LED on hot-swap SCSI backplane.
Action: Have the system serviced.
Function: System Memory Messages (201)
Result Test Specific String
Failed
x
MB DIMM location J22
Note:
x
is the size in megabytes of the DIMM.
Action:
1. Reseat the DIMM in DIMM socket J22.
2. If the problem persists, replace the DIMM.
If the problem persists, have the system serviced.
Failed
x
MB DIMM location J17
Note:
x
is the size in megabytes of the DIMM.
Action:
1. Reseat the DIMM in DIMM socket J17.
2. If the problem persists, replace the DIMM.
If the problem persists, have the system serviced.
128 Netfinity 5000 Server Hardware Information and Procedures