Lathem 24A715M Time Clock User Manual


 
Setting Communications
The [B]=COMMUNICATIONS function is used to enter data transmission speed and a
terminal ID number. Use this function if the clock will be programmed to call the NIST atomic
clock, or if you are using the optional Lathem MasterLink software to program the master clock.
The clock can be set up using RS-232 (serial), RS-485 (networked), or modem (remote) com
-
munications. You must enter the same settings for the Model 24A715M in the programming
software.
You can view the current terminal ID# and baud rate by using the quick command [*]
when the master clock is in clock mode.
Enter the administrative password as shown on page 2-2, then follow the key sequences
below:
Press Display
[#] SELECT FUNCTION CODE
[9] [9]=SYNCH. CLOCKS
[0][0] [B]=COMMUNICATIONS
[#] COMMUNICATIONS SETUP
SELECT BAUD RATE:
[2]400 -OR- [9]600
[2] or [9] Press [2] for 2,400 baud or [9] for 9,600 baud (9,600 is the default)
Note: If the clock will be programmed to call the NIST atomic clock,
you must select 9,600 baud.
9600 (or 2400) BAUD SELECTED
ENTER TERM ID# NNN
[0]...[9] Enter a unique terminal ID# from 00–127 (065 is the default)
[#] PRESS [#] TO CONFIRM
[#] Press [#] to accept or [*] to cancel and try again.
2-8
24A715/24A715M Master Clock Installation Manual