Installation and Configuration
14
7. Insert the equipment, with inner members attached in
Step 5, into the bracket assemblies by inserting the top
and bottom edges of the inner members into the top and
bottom curved tracks of the front members and sliding
the equipment into the rack (see figure at right). Ends of
inner members are tapered to allow the rear of the
equipment to be angled upward before insertion, if space
allows.
Then the rear, bottom edges of the inner members can
be placed into the front edge of the bottom tracks and
the front of the equipment can be tipped up so they are
level to insert the top edges of the inner members before
sliding the equipment into the rack (see figure below
right). The equipment should move smoothly into the
bracket assemblies. If it does not, recheck the alignment
of the front and rear members from Steps 2 and 3.
8. Secure the front of the equipment to the rack mounting
rails to prevent the equipment from sliding out of
position. If securing holes are provided on the front of
the equipment that align with the center holes on the
return flange of the front members, you can use the four
(4) extra M5 screws provided in the kit to secure the
equipment. Otherwise, the equipment should be secured
to the front of the rack with four (4) customer-supplied fasteners.
5.2 Install the Internal Batteries
For ease of installation and configuration, the GXT2-6000RTL630 is shipped without its internal bat-
teries installed. After the UPS is prepared and installed as either a tower or in a rack, install the
GXT2-240BATKIT battery packs.
To install the internal batteries:
!
CAUTION
A battery can present a risk of electrical shock and high short circuit current. Observe the
following precautions before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (cross-head) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is
toxic.
Insert the UPS into the front
members, lift the front ...
... and push it
into the rack.
UPS or
battery
cabinet
Apply
grease
(inside)
A
pp
l
y
grease