Liebert GXT2-6000RTL630 Power Supply User Manual


 
Troubleshooting
34
Using the configuration program, the user may specify the number of GXT2-240VBATTUL external
battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 5 above shows the estimated run times at different loads.
Table 5 Battery run times
Load% 6000VA
Internal Battery
(minutes)
10% 94
20% 46
30% 29
40% 21
50% 17
60% 13
70% 11
80% 9
90% 8
100% 7
Internal Battery
+ 1 External Battery
Cabinet (minutes)
10% 222
20% 124
30% 81
40% 60
50% 49
60% 39
70% 33
80% 28
90% 24
100% 21
Internal Battery
+ 2 External Battery
Cabinets (minutes)
10% 350
20% 197
30% 135
40% 105
50% 85
60% 70
70% 58
80% 50
90% 43
100% 38
Internal Battery
+ 3 External Battery
Cabinets (minutes)
10% 478
20% 269
30% 185
40% 145
50% 123
60% 101
70% 85
80% 73
90% 63
100% 55
Internal Battery
+ 4 External Battery
Cabinets (minutes)
10% 606
20% 341
30% 235
40% 184
50% 156
60% 131
70% 113
80% 97
90% 85
100% 75