Liebert GXT2-6000RTL630 Power Supply User Manual


 
Specifications
36
13.0 SPECIFICATIONS
Table 6 UPS specifications
Model Number GXT2-6000RTL630
Model Rating 6000VA/4200W
Dimensions, in. (mm)
Unit, W x D x H 8.7 x 21.5 x 16.9 (221 x 547 x 430)
Shipping, W x D x H 22.0 x 27.2 x 19.7 (560 x 690 x 500)
Weight, lb (kg)
Unit 57.2 (26)
Shipping 81.5 (37)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 60)
Factory Default VAC 208VAC
User Configurable VAC
208/220/230/240VAC
(May be modified using configuration program)
Operating Voltage Range Without
Battery Operation
176 – 276VAC
Maximum Allowable VAC 276VAC
Input Frequency Without Battery
Operation
40 - 70Hz
Input Power Connection L6-30P Plug (on PD-L630 power distribution box)
Output AC Parameters
Factory Default VAC 208VAC
Output Connections
(2) L6-20R and (2) L6-30R on 12" (300mm) cords
(on PD-L630 power distribution box)
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode
Overload
>200% for 96 milliseconds; 131 - 199% for 2 seconds;
112- 129% for 10 seconds with transfer to bypass
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature 32°F to 104° F (0°C to 40°C)
Storage Temperature 5°F to 122° F (-15°C to 50°C)
Relative Humidity 0-95% non-condensing
Operating Elevation
Up to 6600 ft (2000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
Storage Elevation
Audible Noise
<55 dBA, at 3 ft. (1m) from the rear
<50 dBA, at 3 ft. (1m) from the front or sides
Agency
Safety UL, C-UL Listed to UL1778
EMI/EMC FCC Class B
ESD EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Surge Immunity EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1B