Section 3: Operation
Sequencing Status Screens (cont’d.)
AUTO SEQUENCING ON
DAY 06 OF 15 <00:00>
TEMP STAGING OFF
Each screen is automatically displayed for 3 seconds.
To control the display of the status screens, you can press the
Hold/Sequence button to hold a screen and to manually step through the
screens. Press C to resume automatic sequencing. The system returns to
the Sequencing Status Screens if no control keys have been pressed
during a two minute period.
xx is the number of alarms recorded
since alarm history was last cleared.
See Alarm submenu.
If alarms are present, the last line of the first screen displayed above
reads “ALARMS PRESENT - xx.” Alarm screens are displayed next in
the status sequence. Up to 20 alarms can be displayed, 5 screens of 4
alarms each. Alarms are stored in a First In First Out (FIFO) sequence.
6 • User Manual (9/97)
Select either Auto Sequencing or Standby Testing from the Set Options
Sub-menu.
These functions cannot both be ON
at the same time. Select the function
required for your installation.
Password Screen
If the Password function is enabled, you must enter the valid password
to access the RAC2-8 Main Menu. At the Enter Password screen, type
the established password:
ENTER PASSWORD
>
Units are shipped from the factory with the Password function disabled.
To enable the Password function, press the MENU button to display the
Main Menu, then press 2 SETUP. Follow the instructions on page 12 to
Set Password.
Main Menu
Press the Menu button to display the Main Menu:
MAIN MENU
1. STATUS 2. SETUP
3. ALARMS 4. SET CLOCK
5. OVERRIDE 6. EXIT
Press 9 to display RAC2-8 revision code and date.
Status Sub-menu
From the Main Menu, press 1. STATUS to display the Status Sub-
menu: