Section 3: Operation
Set Modem Options (cont’d)
Hang up on DTR on-off transition
Model 1200: SW1 up and SW10 down
Model 2400: &D3
Track status of carrier detect
Model 1200: SW6 up
Model 2400: &C1
Enable Auto-answer
Model 1200: SW5 up
Model 2400: S0=1
Setup Temp/Humid Options
Press 8 from the Main Menu to display the Setup Temp/Humid Options
screen.
RAC2-8 MAIN MENU
** SET TEMP/HUMIDITY OPTIONS **
1. High Temperature Alarm = 00
2. Low Temperature Alarm = 00
3. High Humidity Alarm = 00
4. Low Humidity Alarm = 00
5. Temperature Staging = OFF
6. Normal Temperature = 70
7. Sensitivity = 02
8. Temp Display (F/C) = F
9. High Humidity Lockout = 60
A. Low Humidity Lockout = 00
<ESC> TO EXIT
High Temperature Alarm = (50-90) >80
** SET TEMP/HUMIDITY OPTIONS **
1. High Temperature Alarm = 80
2. Low Temperature Alarm = 00
3. High Humidity Alarm = 00
4. Low Humidity Alarm = 00
5. Temperature Staging = OFF
6. Normal Temperature = 70
7. Sensitivity = 02
8. Temp Display (F/C) = F
9. High Humidity Lockout = 60
A. Low Humidity Lockout = 00
<ESC> TO EXIT
Temperature Staging = (ENTER 1 for ON, 0 for OFF) >ON
Setup Temp/Humid Options (cont’d)
Temperature and humidity options apply to Zone 1. The system inputs
come from a remote temp/hum sensor. Each alarm can be disabled by
entering 00 as the alarm trip-point. Temperature Staging turns on a
Standby unit when the room temperature exceeds the Normal
Temperature by the number of degrees entered in Sensitivity. Also note
that temperature can be displayed in either degrees F or degrees C.
24 • User Manual (9/97)