Liebert RAC2-8 Power Supply User Manual


 
Section 3: Operation
From the Set Units menu, press 4. SHUTDOWN to display the
Shutdown on Alarm screen:
SHUTDOWN ON ALARM
01-Y 02-Y 03-Y 04-Y
05-Y 06-Y 07-Y 08-Y
1=YES O=NO E=NEXT
Beginning with unit 01, indicate 1 (Yes) or 0 (No) if the unit should
shut down on alarm. When you have selected the shutdown status for
the last unit, the RAC2-8 displays the Set Units menu.
When you have configured the delays, from the Set Units menu, press 5
to return to the Set Options Menu.
2. DELAYS
From the Set Options Sub-menu, press 2. DELAYS to display the Set
Delays menu:
SECTION 4 — GLOSSARY OF
CONTROL FUNCTIONS
includes a functional description
of each delay.
SET DELAYS MENU
1. ALARM 2.HOLD
3. UNIT RESTART
5. RETURN
From the Set Delays menu, press 1. ALARM to configure the Alarm
Delay:
Set Options Sub-menu (cont’d)
ENTER ALARM DELAY
<10.0> XX.X MINUTES
THEN PUSH ENTER
PUSH CLEAR TO RETURN
Enter the desired time for the alarm delay. The default is 10 minutes.
Press E to accept the new delay, then press C to return to the Set Delays
menu.
From the Set Delays menu, press 2. HOLD to configure the Hold
Delay:
ENTER HOLD DELAY
<10.0> XX.X MINUTES
THEN PUSH ENTER
PUSH CLEAR TO RETURN
Enter the desired time for the hold delay. The default is 10 minutes.
Press E to accept the new delay, then press C to return to the Set Delays
menu.
10 User Manual (9/97)