Section 3: Operation
1. F
2. C
5. RETURN
From the T/H menu, press 4. LOCK to configure the optional Humidity
Lockout feature:
HUMIDITY LOCKOUT
SET HI>00 LOW>00
(RANGE 20-80) 00=OFF
E=NEXT C=RETURN
Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS
for details on the Humidity Lockout feature.
Set Options Sub-menu (cont’d)
4. STANDBY
From the Set Options Sub-menu, press 4. STANDBY to display the
Standby Options menu:
STANDBY OPTIONS MENU
1. AUTO SEQUENCE UNIT
2. AUTO STANDBY TEST
5. RETURN
From the Standby Options menu, select Auto Sequencing, Standby
Testing, or neither. These functions cannot both be active (ON) at the
same time.
Select the desired function. If you select 1. AUTO SEQUENCE UNIT,
you must also configure a schedule for your installation:
AUTO SEQUENCING ON
EVERY <0-99> XX DAYS
AT TIME 00:00
00=OFF E=NEXT C=RTN
5. PASSWORD
From the Set Options Sub-menu, press 5. PASSWORD to display the
Set Password menu:
SET PASSWORD MENU
1. NEW PASSWORD
5. RETURN
The Password function provides security to the RAC2-8 so that only
authorized personnel can make Setup changes to the system.
12 • User Manual (9/97)