Operating Instructions 13
Table 5 Example View Event Log Response
DATE TIME DESCRIPTION Logged Events include:
10/21/97 16:34:39 Transferred to Preferred Preferred Source Fail
Preferred Source Available
Alternate Source Fail
Alternate Source Available
Out of Sync
In Sync
Peak Overload
Peak Overload Gone
Transfer Inhibit
OK to Transfer
Power Supply Fault
Power Supply OK
Switch in Normal Mode
Manual Transfer to S1
Manual Transfer to S2
Bypass to S1
Bypass to S2
Transferred to Alternate
Transferred to Preferred
Transfer Test Initiated
Transfer Test Pended
Transfer Test Passed
Transfer Test Failed
10/21/97 16:34:39 Transfer Test Passed
10/21/97 16:34:39 Transferred to Alternate
10/21/97 16:34:38 Transfer Test Initiated
10/21/97 16:34:38 Alternate Source Available
09/27/97 07:22:11 In Sync
09/27/97 07:21:08 Out of Sync
06/01/97 02:10:32 Transferred to Preferred
06/01/97 02:10:29 Preferred Source Available
06/01/97 01:29:13 Transferred to Alternate
06/01/97 01:29:13 Preferred Source Fail
Table 6 Example View Settings Response
CURRENT SETTINGS:
System Time: 10/21/97 16:23:54
Nominal Voltage: 120
Amps: 24
Frequency: 60
Phase: 1
Neutral: YES
Unit Type: UNDERFLOOR
Sync Window: 10
Auto Retransfer: ENABLED
Retransfer Delay: 5
Current Inhibit: 5
Inhibit Type: MANUAL
Transfer Test: ENABLED
Next Test: 10/01/97 23:59:58
Test Interval: 90
Preferred Source S1