Magnetek Series 3 Network Hardware User Manual


 
Impulse DataLogger Series 3 Instruction Manual 2/1/05
8 of 16
The Fault History provides the data for reviewing recorded faults and information
on each fault occurrence.
-FAULT HISTORY -
Flt: 1 OF 6
Run: 5
Ext Fault S7
01/16/04 02:37
01/28/04 08:44:13
- FAULT HISTORY -
U2-03: 030.00 Hz
U2-04: 017.60 Hz
U2-05: 002.56 A
U2-06: 0000
01/28/04 08:44:13
- FAULT HISTORY -
U2-07: 000.0 VAC
U2-08: 000.0 VDC
U2-09: 000 KW
U2-10: 000 %
01/28/04 08:44:13
Date & Time:
Used to time stamp all
history and trace data.
Fault number
Run where fault
occured
Fault Description
Date and time of fault
U2-03 = Frequency Reference
U2-04 = Output Frequency
U2-05 = Output Amps
U2-06 = Motor Speed
U2-07 = Output Voltage
U2-08 = DC Bus Voltage
U2-09 = Output Kw
U2-10 = Torque Reference
- FAULT HISTORY -
U2-11: 00000000
U2-12: 00000000
U2-13: 00000000
01/28/04 08:44:13
U2-11 = Input terminal status
U2-12 = Output terminal status
U2-13 = Inverter status
FAULT AND ALARM FILTERS
To turn off the recording of any faults or alarms, go to “Settings”, “Fault Filters” or
“Alarm Filters” and press enter. Scroll up or down through the listing of
faults/alarms. If you would like to filter out a fault from being recorded then press
the enter key when the cursor is next to the desired fault. A check mark on the left
hand side will indicate that the fault has been selected to be filtered out. Alarms
would be selected in the same manner.