MGE UPS Systems 30A Power Supply User Manual


 
34020113EN/AA - Page 27
6. Appendix
6.1 Technical data
Output currents and voltage
Rated output current:
Input and output voltage:
Rated operating voltage:
Maximum voltage:
Minimum voltage:
Rated frequency:
30 A
380 V / 400 V / 415 V
498 V (415 V +20%)
247 V (380 V -35%)
50 or 60 Hz (45 Hz minimum, 66 Hz maximum)
60 A 100 A 160 A 250 A 400 A 600 A
Permissible-overload curve
During an overload, transfer between sources is disabled.
Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.
Thermal characteristics
(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.
Heat losses
(1)
:
at rated power:
at 50% rated power:
Required ventilation:
195 W
150 W
350 m
3
/h
295 W
195 W
350 m
3
/h
430 W
260 W
350 m
3
/h
615 W
350 W
1600 m
3
/h
920 W
495 W
1600 m
3
/h
1420 W
735 W
2300 m
3
/h
2150 W
1070 W
2300 m
3
/h
Noise level
Recommended protection devices upstream of Upsilon STS
Cable sizes
Noise in dB (ISO 3746):
Cross-sectional area in mm
2
:
50 50 50 120 120 240 240
Type of circuit breaker:
TNS system:
TNC system:
Trip unit:
Thermal setting:
Magnetic setting:
C60L 32A
curve C
1.05 In
10xIn
NS100H 4P 4D
NS100H 3P
STR22SE
1.05 In
10xIn
NS160H
4P 4D
NS160H
3P
STR22SE
1.05 In
10xIn
NS400H
4P 4D
NS400H
3P
STR23SE
1,05 In
10xIn
NS250H
4P 4D
NS250H
3P
STR22SE
1.05 In
10xIn
NS630H
4P 4D
NS630H
3P
STR23SE
1.05 In
10xIn
55 55 55 59 59 59 59
In
2 In
4 In
8 In
32 In
16 In
t(s)
0.01 s 0.1 s 1 s 10 s 100 s 1000 s