Network Shutdown Module V3 – User Manual - APC # 990-3630 (MGE # 34 003 934 XU / AB) Page 52/66
7.8.2 Events Tab
In this tab you can associate the action with the event(s) that will trigger the action :
Events Tab
ω Select the action from the left hand side of the above screen
=> The list of events already associated with this event appear (checked boxes)
ω Check (or uncheck) the events you wish to associate with this action
ω Save your configuration using Save change(s) button.
For each event, an on-line help is displayed when the mouse pointer is positioned over it.
Following events can trig the actions. They are classed by category:
7.8.2.1 Notification alarms
These alarms are mainly dedicated to trigger user notification actions:
ω Utility failure The system is now powered by the UPS battery
or [by the utility]
ω 'Run time to shutdown' alarm Alarm to indicate the remaining time before system shutdown
ω UPS fault (internal fault or battery fault) Internal UPS fault or battery fault was detected
or [end of Internal/Battery fault]
ω UPS overload The output is over loaded
or [the output load is correct]