Mitsubishi 9800A Series Power Supply User Manual


 
MITSUBISHI ELECTRIC 9800A SERIES UPS
MITSUBISHI
ELECTRIC
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-6
TABLE 3.5 Crimp Type Compression Lug
WIRE
SIZE
WIRE
STRAND
RECOMMENDATION CRIMP TOOL REQUIRED
BURNDY TYPE Y35 OR Y46
(CODE) CLASS VENDOR CAT. NO. COLOR KEY DIE INDEX
1 B
I
BURNDY
ILSCO
BURNDY
YA1C
CRA-1L
YA25-LB
GREEN
GREEN
---
11 / 375
11 / 375
1019
1/0 B
I
BURNDY
ILSCO
BURNDY
YA25
CRA-1/OL
YA25-LB
PINK
PINK
---
12 / 348
12 / 348
1020
2/0 B
I
BURNDY
ILSCO
BURNDY
YA26
CRA-2/OL
YA27-LB
BLACK
BLACK
---
13
13
1021
3/0 B
I
BURNDY
ILSCO
BURNDY
YA27
CRB-3/OL
YA28-LB
ORANGE
ORANGE
---
14 / 101
14 / 101
1022
4/0 B
I
BURNDY
ILSCO
BURNDY
YA28
CRB-4/OL
YA29-LB
PURPLE
PURPLE
---
15
15
1023
250 MCM B
I
BURNDY
ILSCO
BURNDY
YA29
CRA-250L
YA30-LB
YELLOW
YELLOW
---
16
16
1024
300 MCM B
I
BURNDY
ILSCO
BURNDY
YA30
CRA-300L
YA32-LB
WHITE
WHITE
---
17 / 298
17 / 298
1026
350 MCM B
I
BURNDY
ILSCO
BURNDY
YA31
CRA-350L
YA34-LB
RED
RED
---
18 / 324
18 / 324
1027
400 MCM B
I
BURNDY
ILSCO
BURNDY
YA32
CRA-400L
YA36-LB
BLUE
BLUE
---
19 / 470
19 / 470
1027
500 MCM B
I
BURNDY
ILSCO
BURNDY
YA34
CRA-500L
YA38-LB
BROWN
BROWN
---
20 / 299
20 / 299
1029
NOTE: When using crimp type lugs, the lugs should be crimped to the specifications given in the
manufacturer's instructions for both crimp tool and lug.
FIGURE 3.1 UPS Terminal Designation
52S
Output
52C
UPS ModuleBattery cabinet
CB1
CB2
Terminals:
BP,BN
Terminals:
A50,B50,C50,
N50
Static Transfer
Switch
CB3
AC Bypass
In
p
ut
AC input
Terminals:
A40,B40,C40,N40
Terminals:
A, B, C