6-4-1 FINS Communications Service
The FINS communications service is a communications protocol developed
by OMRON for FA control devices. It can be used for reading from and writing
to PLC memory, or for controlling various operations, without having to create
a user’s program at the PLC. The FINS communications service has its own
independent address system which does not rely on the actual network
address system, so it can carry out communications in the same way regard-
less of whether the PLC at the local node is on a Controller Link Network or
some other FA network (e.g., SYSMAC NET or SYSMAC LINK). For details
on FINS commands, refer to the FINS Commands Reference Manual (W227).
6-4-2 Sending and Receiving FINS Commands and Responses
FINS commands can be sent by using the CMND instruction with a CVM1,
CV-series, CS/CJ-series, or CQM1H-series PLC. The following diagram
shows the data format for sending FINS commands and receiving responses.
The data that is sent and received is all hexadecimal unless otherwise noted.
Command
Response
Word
Word
1 byte
FINS header
Automatically prepared and added.
2 bytes 2,000 bytes max.
Command code Text
Controller
Link Unit
CPU Unit
CS/CJ, CVM1,
CV-series,
or CQM1H-
series PLC
Computer
Controller Link
Support Board
2 bytes 2 bytes 1,998 bytes max.
FINS header
Automatically
added.
Command
code
Response
code
Text
1 byte
Response
Command
Automatically pre-
pared and added.
1 byte 1 byte
@CMND
S
S+1
S+2
15 87
D
D+1
D+2
15 87
S
D
C
0