Omron CS1W-CLK21-V1 Network Card User Manual


 
72
Wiring Section 3-3
8. Do not place any object on the power cable.
9. Check that connectors are correctly attached before using the Unit.
Power Supply Specifications
The power supply to the Repeater Unit must meet the following specifications.
The following Power Supply Unit is recommended:
OMRON S82K Series
Laying Optical Cable (CS1W-RPT02/03 Only)
Optical fiber cable (H-PCF or GI) can be used to create an optical connection
in part of a wired network.
CS1W-RPT02 (H-PCF)
Note 1. Always use the specified Optical Fiber Cables.
2. The maximum distance between nodes depends on how the cable is con-
nected. For details, refer to the applicable Optical Fiber Cable (H-PCF)
manual.
Connection Procedure Use the following procedure to connect Optical Fiber Cables to a Unit.
1,2,3... 1. Tighten screws in the mounting brackets so that the through-holes on the
terminal are on the top and bottom and then affix hexagonal nuts from the
opposite side of the terminal.
2. Insert bushing to the mounting bracket and secure the Unit with screws.
3. Pass the tension member through the through-holes, and tighten the ter-
minal screws to affix the tension member.
4. Affix the cable to the mounting bracket so that it is clamped by the bracket.
Item CS1W-RPT01
Wire-to-Wire
Repeater Unit
CS1W-RPT02
Wire-to-Optical (H-
PCF) Repeater Unit
CS1W-RPT03
Wire-to-Optical (GI)
Repeater Unit
Power supply volt-
age
24 V DC
Allowable power
supply voltage
range
20.4 to 26.4 V DC (24 V DC, 15% to 10%)
Current consump-
tion
24 V DC at 60 mA
max.
24 V DC at 60 mA
max.
24 V DC at 70 mA
max.
Inrush current 2.5 A max. (24 V DC with rise time 5 ms)
H-PCF cable
SL1
SL2
SL1
SL2
Wired Controller
Link Unit
Wired Controller
Link Unit
CS1W-RPT02
Repeater Unit
CS1W-RPT02
Repeater Unit