Omron CS1W-CLK21-V1 Network Card User Manual


 
359
Memory Areas Appendix B
Local Data Link Participation Status: CIO 1500 + 25 × (Unit No.) + 6 (See page 304.)
Data Link Status: CIO 1500 + 25
× (Unit No.) + 7 to + 22 (See pages 156, 305.)
When the first data link status word for manually set data link tables or for automatically set data links is not set
or is set to 0, the data link status is stored in the words shown below.
1: Local node data link participating
0: Local node data link not
p
artici
p
atin
g
or data link inactive
Node 2
Node 4
Node 6
Node 8
Node 10
Node 12
Node 14
Node 16
Node 18
Node 20
Node 22
Node 24
Node 26
Node 28
Node 30
Node 32
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error
0: Normal
1: Error
Error: Offset exceeds
number of send words.
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.
Remaining receive area
0: Not remaining
1: Remaining
Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.
Node 1
Node 3
Node 5
Node 7
Node 9
Node 11
Node 13
Node 15
Node 17
Node 19
Node 21
Node 23
Node 25
Node 27
Node 29
Node 31
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+22