Panasonic FP2 Computer Accessories User Manual


 
FP2CCU
Specifications
6 8
6.3 Table of MEWTOCOLCOM Error Code
61 Data Error:
Situation
There is an error in the contact number and/or data number specification.
There is an error in the decimal or hexadecimal format specification for
the data.
Example of error
This occurs if the data register specification is in hexadecimal format
when an RD command is sent.
ERR LED on the FP2 Computer Communication Unit
Off
62 Registration Error:
Situation
Too many registrations have been entered, or a registration has not been
entered.
Example of error
This occurs if the number of data registered exceeds 16 words when an
MD command is sent.
ERR LED on the FP2 Computer Communication Unit
Off
63 PC Mode Error:
Situation
The PLC is in a mode in which the sent command cannot be processed.
Example of error
This occurs if the CPU unit side is in the RUN mode when a WR
command is sent.
ERR LED on the FP2 Computer Communication Unit
Off
65 Protect Error:
Situation
Write operation was performed to the program area or system register in
the memory protect state.
Example of error
This occurs if a password has been specified for the CPU when an RR
command is sent.
ERR LED on the FP2 Computer Communication Unit
Off