Paradyne 3611 Network Card User Manual


 
COMSPHERE –48 Vdc Central Office Power Unit
2-10 May 1998 3000-A2-GB41-40
P20 P19
497-13673-0
1
P3
(OUTPUT)
CAPTIVE
SCREW
P6
(OUTPUT)
–48VDC B
(INPUT)
CAPTIVE
SCREW
BACKPLANE
CONNECTOR
CABLE
ASSEMBLIES
NETWORK
MANAGEMENT
CONNECTOR
ALARM B
ALARM A
–48VDC A
(INPUT)
Figure 2-4. COMSPHERE 3000 Series Carrier (Rear)
Providing Power to a CO Power Unit
After the CO Power Unit installation procedure is
completed, you must provide power to the unit. There are
a number of powering options available depending upon
your configuration.
NOTE
The option strap settings are
factory set for the Basic mode of
operation.
To provide power to the CO Power Unit operating in
Basic mode:
" Procedure
1. Use one connector housing (AMP part
number 1-480698-0) and two crimp-type contacts
(AMP part number 350550-1) to attach the
connector to your –48 Vdc power input cable.
Note that you need a hand crimping tool (AMP
part number 90296-2 or equivalent) to build the
connector.
(The contacts are crimp type and are intended for
use with 20 AWG through 14 AWG wire with a
maximum insulation diameter of .130 inches. For
additional information, see Appendix A of this
guide.)
2. Provide external fusing, if desired. (The fuse
shown in Figure 2-5 is optional as per your
requirements.) The optional fuse should have a
rating of 6 amperes, 250 volts, and be a fast-acting
type. Use a fuse similar to Littlefuse #312006.
3. Plug the input power cable to either the
–48VDC A connector or the –48VDC B
connector. See Figure 2-5. (The option strap
settings for this power option are listed in
Table 2-2.)