Powerware FE/QFE 500VA Power Supply User Manual


 
External Bypass Switch Installation
39
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
50 Hz 220, 230, or 240 Vac Input and Output
Figure 11. QFE 500 VA–3.1 kVA UPS with External Bypass Switch
Table 16. Input Current - Size Overcurrent Protection According To Local Code
Voltage Charger 500 VA 700 VA 850 VA 1.15 kVA 1.4 kVA 1.8 kVA 2.1 kVA 3.1 kVA
220 Vac
Standard 2.6A 3.9A 4.4A 4.9A 5.7A 7.9A 8.2A 13A
15A 4.7A 6.0A 6.5A 7.0A 7.8A 14A 15A 19A
230 Vac
Standard 2.5A 3.8A 4.2A 4.6A 5.4A 7.5A 7.8A 12A
15A 4.6A 5.9A 6.3A 6.7A 7.5A 14A 14A 18A
240 Vac
Standard 2.4A 3.5A 4.0A 4.4A 5.2A 7.2A 7.4A 12A
15A 4.6A 5.7A 6.2A 6.6A 7.4A 14A 14A 19A