Powerware FE/QFE 500VA Power Supply User Manual


 
Internal Bypass Switch Installation
51
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
60 Hz 208 or 480 Source/240 Vac Input - 120/240 Vac Output (with Transformer)
Figure 19. FE 4.3–18 kVA UPS with Internal Bypass Switch
Table 25. Minimum Recommended Circuit Breakers for 240 Vac
Charger 4.3 kVA 5.3 kVA 7kVA 10 kVA 12.5 kVA 18 kVA
Standard 20 25 35 50 70 100
10A 20 30 35 60 70 100
20A 25 35 35 60 80 110