Powerware FE/QFE 500VA Power Supply User Manual


 
Internal Bypass Switch Installation
52
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide : Rev A www.powerware.com
QFE: 50 Hz 220, 230, or 240 Vac Input and Output
FE: 60 Hz 220 Vac Input and Output
For FE 60 Hz 220 Vac, use only a BBM switch.
Figure 20. FE or QFE 4.3–18 kVA UPS with Internal Bypass Switch
Table 26. Input Current - Size Overcurrent Protection According To Local Code
Voltage Charger 4.3 kVA 5.3 kVA 7kVA 10 kVA 12.5 kVA 18 kVA
60 Hz
2
2
0
V
Standard 17A 21A 27A 41A 53A 81A
220 Vac
10A
18A 23A 28A 49A 60A 85A
20A 20A 25A 30A 52A 65A 89A
50 Hz
2
2
0
V
Standard 19A 21A 27A 43A 55A 81A
220 Vac
10A
22A 23A 28A 46A 58A 84A
20A 23A 25A 29A 51A 63A 89A
50 Hz
2
3
0
V
Standard 18A 20A 26A 41A 53A 78A
230 Vac
10A
20A 22A 27A 44A 56A 81A
20A 21A 24A 28A 49A 60A 85A
50 Hz
2
4
0
V
Standard 17A 19A 24A 39A 51A 75A
240 Vac
10A
19A 21A 26A 43A 54A 78A
20A 20A 23A 27A 47A 58A 82A