Table 7. Battery
Configuration 500 VA: (2) 6V, 9 Ah internal battery
750 VA: (4) 6V, 7.2 Ah internal batteries
1000 VA: (4) 6V, 9 Ah internal batteries
1500 VA: (6) 6V, 9 Ah internal batteries
Voltage 500VA: 12 Vdc
750–1000 VA: 24 Vdc
1500 VA: 36 Vdc
Type Sealed, maintenance-free, valve-regulated, lead-acid
Charging Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at
nominal line and no supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Battery Run Times 5 minutes, typical at full load