Schneider Electric LUFP9 Network Router User Manual


 
75
6. Configuring the Gateway
The LUFP9 gateway’s default configuration includes two “Transaction” commands. These are aperiodic
commands used for reading and writing the value of a Modbus slave parameter (necessarily a TeSys U motor
starter with the default configuration). They are configured solely for the “TeSys U n°1” node, as the address of
the slave is controlled by the DeviceNet master via the first byte of the “Data” field, which corresponds to the
“Slave Address” field in standard Modbus commands. This allows the DeviceNet master to send this command
to all of the Modbus slaves, slave by slave, through the first byte of the “Data” field. The remaining fields of the
frames used by these two commands are also placed in the same “Data” field. So the DeviceNet master has
access to all of the content of the frames in these two commands, excluding the checksum.
6.12. Configuring the General Characteristics of the Gateway
This operation relates to the gateway’s general characteristics (“Fieldbus”
to “Sub-Network” elements), whereas the previous chapters described the
configuration of the Modbus slaves (elements located under the “Sub-
Network” element).
The “Fieldbus” element describes the upstream network, that is to say the
DeviceNet network in the case of the LUFP9 gateway.
The “ABC” and “Sub-Network” elements describe the downstream
network, that is to say the Modbus RTU network in the case of the LUFP9
gateway, and allow you to identify the software version in the gateway.
The configuration of these three elements, plus the commands they give
access to, are described in the next three chapters.
6.12.1. “Fieldbus” element
Below this element there is a list of the mailboxes configured by default. These elements are not described here,
as they are only designed for the internal management of the gateway. These mailboxes can neither be changed
nor deleted. Both their number and their nature depend on the type of upstream network.
When the “Fieldbus” element is selected, you can select the
type of upstream network. With the LUFP9 gateway, you
must select the “DeviceNet” network.
When the “DeviceNet” network is selected, you have access
to an additional field, known as “IO Sizes”.
Its value,
“Automatic,” must not be changed!
If your PC is connected to the gateway using the PowerSuite cable and you are using AbcConf in “on-line” mode
when AbcConf starts up, the type of upstream network will be automatically detected.