PART 5: ZONE PROGRAMMING
The Spectra control panel’s zone assignment depends on where the detection devices are connected (see Table 4).
5.1 WHAT IS AN EXPANSION INPUT?
An expansion input allows you to connect modules to the system to increase the number of zones available up to 16
zones. Each hardwired input on a zone expansion bus module or wireless transmitter used by a wireless bus
module can be assigned to an expansion input. The expansion inputs can be used in any combination. For example,
5 wireless transmitters and 3 hardwire inputs can be assigned to the expansion inputs. Spectra control panels
cannot support more than eight expansion inputs. Refer to the appropriate module’s Instruction Sheet for details.
Do not assign inputs from different modules to the same expansion input.
5.2 REASSIGN KEYPAD ZONE 2
Section [126]: General Options
Option [7] OFF = Reassign Keypad Zone 2 Disabled (default)
Option [7] ON = Reassign Keypad Zone 2 Enabled
Reassign Keypad Zone 2 changes the keypad zone into an expansion input. In
Table 4 above, the effects of enabling this feature are shown. For example, when
option [7] is enabled in control panel 1738, Zone 16 moves to Expansion Input 1
(see Table 5). Then, you are able to use Expansion Input 1
Table 4:
Zone Recognition Table
Device
connected to
which input?
1728/EX 1728 1728/EX 1728
With Re-assign Keypad
Zone 2 enabled (p. 19)
1738/EX 1738 1738/EX 1738
With Re-assign Keypad
Zone 2 enabled (p. 19)
NO ATZ WITH ATZ NO ATZ WITH ATZ NO ATZ WITH ATZ NO ATZ WITH ATZ
Control Panel
Input 1 = Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 6 Zone 1 Zone 1 & 8 Zone 1 Zone 1 & 8
Input 2 = Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 7 Zone 2 Zone 2 & 9 Zone 2 Zone 2 & 9
Input 3 = Zone 3 Zone 3 & 8 Zone 3 Zone 3 & 8 Zone 3 Zone 3 & 10 Zone 3 Zone 3 & 10
Input 4 = Zone 4 Zone 4 & 9 Zone 4 Zone 4 & 9 Zone 4 Zone 4 & 11 Zone 4 Zone 4 & 11
Input 5 = Zone 5 Zone 5 & 10 Zone 5 Zone 5 & 10 Zone 5 Zone 5 & 12 Zone 5 Zone 5 & 12
Input 6 = N/A N/A N/A N/A Zone 6 Zone 6 & 13 Zone 6 Zone 6 & 13
Input 7 = N/A N/A N/A N/A Zone 7 Zone 7 & 14 Zone 7 Zone 7 & 14
Keypad
Zone 1 = Zone 6 Zone 11 Zone 6 Zone 11 Zone 8 Zone 15 Zone 8 Zone 15
Zone 2 = Zone 7 Zone 12 N/A N/A Zone 9 Zone 16 N/A N/A
Expansion
Input 1 = Zone 8 Zone 13 Zone 7 Zone 12 Zone 10 N/A Zone 9 Zone 16
Input 2 = Zone 9 Zone 14 Zone 8 Zone 13 Zone 11 N/A Zone 10 N/A
Input 3 = Zone 10 Zone 15 Zone 9 Zone 14 Zone 12 N/A Zone 11 N/A
Input 4 = Zone 11 Zone 16 Zone 10 Zone 15 Zone 13 N/A Zone 12 N/A
Input 5 = Zone 12 N/A Zone 11 Zone 16 Zone 14 N/A Zone 13 N/A
Input 6 = Zone 13 N/A Zone 12 N/A Zone 15 N/A Zone 14 N/A
Input 7 = Zone 14 N/A Zone 13 N/A Zone 16 N/A Zone 15 N/A
Input 8 = Zone 15 N/A Zone 14 N/A N/A N/A Zone 16 N/A
Table 5:
Example
1738
WITH ATZ
OFF ON
Zone 15 Zone 15
Zone 16 N/A
N/A Zone 16
When Reassign Keypad Zone 2 is enabled, the Keypad Tamper
Supervision (see page 44) for keypad zone 2 is lost. Keypad Tamper
Supervision will
ONLY function on Keypad Zone 1.