SpectraLink 1738EX Computer Hardware User Manual


 
SPECTRA SERIES 35
8.2.10 SYSTEM TROUBLE REPORT CODES
Section [205] to [207]
Whenever the system generates one of the instances listed below, the control panel can send the
appropriate report code to the central station identifying the type of system trouble.
Section [205]
Future use
AC FAILURE: The control panel has detected a loss of AC power. Transmission of this report code can
be delayed (see Power Failure Report Delay on page 39).
BATTERY FAILURE: backup battery is disconnected or battery voltage is 10.5V.
AUXILIARY SUPPLY: Auxiliary power supply has overloaded (current consumption is >1.1A).
Section [206]
BELL OUTPUT OVERLOAD: Bell/siren output has overloaded (see page 10).
BELL OUTPUT DISCONNECTED: Devices connected to the Bell Output have been disconnected.
TIMER LOSS: The control panel has detected a loss in time or clock failure (see page 44)
FIRE LOOP TROUBLE: The control panel has detected a tamper trouble on a fire zone.
Section [207]
WIRELESS LOW BATTERY: The battery voltage of a Liberator or Omnia wireless transmitter (motion
detector or contact switch) has dropped below recommended limits.
MODULE FAULT: Will report if all keypads connected to the control panel have been disconnected or if a
module with its corresponding supervision option enabled in the control panel (see pages 45 and 46) is
disconnected.
PRINTER FAULT: An error has occurred on the Printer Bus Module.
FAIL TO COMMUNICATE: The control panel has failed all attempts to communicate with the central
station. The report code will be transmitted upon the next successful attempt.
8.2.11 SYSTEM TROUBLE RESTORE CODES
Sections [208] to [210]
Whenever the system restores one of the troubles listed in section 8.2.10, the control panel can send the
appropriate report code to the central station identifying the type of system trouble restore. If Telephone
Line Monitoring is enabled (see page 40), the control panel can also transmit a TLM Restore report code.
8.2.12 SPECIAL REPORTING CODES
Sections [211] to [213]
Whenever the system generates one of the instances listed below, the control panel can send the
appropriate report code to the central station identifying the type of system occurrence.
Section [211]
COLD START: The control panel was completely shutdown (no battery, no AC) and then was re-started.
TEST REPORT: A test report has been generated automatically (see page 39).
Not available
PC EXIT: The control panel has ended communication with WinLoad.
Section [212]
INSTALLER IN: Installer has entered the programming mode.
INSTALLER OUT: Installer has exited the programming mode.
Future use
Future use
Section [213]
TX SUPERVISION LOSS: Wireless Transmitter Supervision (see SPC-319 Instruction Sheet) has been
enabled and a transmitter is no longer communicating with the system.
TX SUPERVISION RESTORE: Reports when the above trouble has been restored
Future use
Future use