6.6 TIMED AUTO-ARMING
Section [133] = Partition 1, [134] = Partition 2
Option [1] OFF = Timed Auto-Arming Disabled (default)
Option [1] ON = Timed Auto-Arming Enabled
Each partition can be programmed to arm every day at the time specified by the Auto-Arm Timer. The Auto-Arming
Options (see section 6.8) determine the partition's arming method. Any open zones detected when a partition is
Auto-Armed will be bypassed regardless of their definition (except 24hr. zones). The control panel will enter a 60-
second Exit Delay period before arming the system. At this point, Auto-Arming can be cancelled by entering a valid
access code. Once the partition has successfully armed, the control panel can transmit the Timed Auto-Arming
report code programmed in section [172].
Example: To automatically arm partition 2 everyday at 6:15PM, enable Timed Auto-Arming for partition 2 by turning
on option [1] in section [134]. Then key in 18:15 into section [112].
6.6.1 AUTO-ARM TIMER
Section [111] = Partition 1, [112] = Partition 2
Select the section corresponding to the desired partition and program the time (use the 24-hour clock i.e.
6:30PM = 18:30) that you wish the control panel to attempt to arm the selected partition and/or send the
Late to Close report code.
6.7 NO MOVEMENT AUTO-ARMING
Section [133] = Partition 1, [134] = Partition 2
Option [2] OFF = No Movement Auto-Arming Disabled (default)
Option [2] ON = No Movement Auto-Arming Enabled
If no movement occurs in a partition's protected area for the period specified by the No Movement Timer (see
below), the control panel can automatically arm that partition. The Auto-Arming Option described in section 6.8 of
this manual determines the partition's arming method. Any open zones detected when a partition is Auto-Armed will
be bypassed regardless of their definition (except 24hr. zones). Upon arming, the control panel will transmit the No
Movement report code if programmed in section [172]. Regardless of whether the system was successfully armed
or not, the control panel will always transmit the No Movement report code if programmed in section [172]. If No
Movement Auto-Arming is disabled, the control panel will still send the No Movement report code at the time
specified by the No Movement Timer.
Example: To arm partition 1 whenever there is no movement for a period of 4 hours, enable No Movement Auto-
arming for partition 1 by turning on the [2] Option in section [133]. Then in section [075] enter 016 (16x15min. =
240min. = 4 hours).
6.7.1 NO MOVEMENT TIMER
Section [075] = Partition 1, [076] = Partition 2
001 to 255 x15min., Default = disabled
Select the section corresponding to the desired partition and program the interval of time without
movement you wish the control panel to wait before arming and/or sending the No Movement report code.
If No Movement Auto-Arming is disabled, the control panel can still send the No Movement report code
when no movement has been detected for the period specified by the No Movement Timer.
6.8 AUTO-ARMING OPTIONS*
Section [133] = Partition 1, [134] = Partition 2
Option [3] OFF = Regular Arming (default)
Option [3] ON = Stay Arming
When using Timed Auto-Arming or No Movement Auto-Arming (see section 6.6 and section 6.7), the control panel
can Regular or Stay Arm (see page 52) the selected partition.
* Not to be used with UL installations