SSI America ERP2U Power Supply User Manual


 
SSI
ERP2U Power Supply Design Guide, V2.31
- 11 -
The power supply shall operate within all specified limits over the T
op
temperature range. All airflow shall pass
through the power supply and not over the exterior surfaces of the power supply.
Table 2: Thermal Requirements
ITEM DESCRIPTION MIN MAX UNITS
T
op
Operating temperature range. 0 50
°C
T
non-op
Non-operating temperature range. -40 70
°C
The power supply must meet UL enclosure requirements for temperature rise limits. All sides of the power supply
with exception of the air exhaust side, must be classified as “Handle, knobs, grips, etc. held for short periods of
time only”.
5 AC Input Requirements
STATUS
Required
The power supply modules shall incorporate universal power input with active power factor correction, which shall
reduce line harmonics in accordance with the EN61000-3-2 and JEIDA MITI standards.
5.1 AC Inlet Connector
STATUS
Required
The AC input connector shall be an IEC 320 C-14 power inlet. This inlet is rated for 15 A/250 VAC. This
connector may be located on the module or on the cage.
5.2 Redundant AC Inlets
STATUS
Recommended
The power supply assembly may have dual redundant AC inlets. The power supply shall be able to operate over
its full, specified range of requirements with either or both AC input powered. If there is a loss of one AC inlet the
power supplies shall continue to operate with no interruption of performance. It is required that all redundant
power supply modules be present to support redundant AC inlets.
5.3 AC Input Voltage Specification
STATUS
Required
The power supply must operate within all specified limits over the following input voltage range. Harmonic
distortion of up to 10% THD must not cause the power supply to go out of specified limits. The power supply shall
operate properly at 85 VAC input voltage to guarantee proper design margins.