SSI
ERP2U Power Supply Design Guide, V2.31
- 14 -
recoverable
Table 6: AC Line Surge Transient Performance
AC Line Surge
Duration Surge Operating AC Voltage Line Frequency Performance Criteria
Continuous 10% Nominal AC Voltages 50/60 Hz No loss of function or performance
0 to ½ AC
cycle
30% Mid-point of nominal AC
Voltages
50/60 Hz No loss of function or performance
5.10 AC Line Fast Transient Specification
STATUS
Recommended
The power supply shall meet the EN61000-4-5 directive and any additional requirements in IEC1000-4-5:1995
and the Level 3 requirements for surge-withstand capability, with the following conditions and exceptions:
• These input transients must not cause any out-of-regulation conditions, such as overshoot and
undershoot, nor must it cause any nuisance trips of any of the power supply protection circuits.
• The surge-withstand test must not produce damage to the power supply.
• The supply must meet surge-withstand test conditions under maximum and minimum DC-output load
conditions.