Site Evaluation – Internal Considerations
Floor Loading Specifications and References
Table 4-3. VSM5-VTSS Floor Loading Specifications
Basic Floor Load* Maximum Superimposed Floor Load
#
730 kg/m
2
(149 lbs./ft
2
) 485 kg/m
2
(99 lbs./ft
2
)
Notes:
•
* Load over footprint surface area (7093.7 cm
2
/1099.5 in
2
) of an unpackaged VSM5-VTSS cabinet, with a maxi-
mum weight of 445 kg/982 lbs., i.e., a VTSS with 64 array disk drives.
•
#
Assumes minimum Z+Z axis dimension of 185.3 cm/73.0 in. (i.e., cabinet depth 77.1 cm/30.4 in. + front service
clearance of 54.1 cm/21.3 in. + rear service clearance of 54.1 cm/21.3 in.), minimum X+X axis dimension of 104.9
cm/41.2 in. (i.e., cabinet width 92.1 cm/36.3 in. + left clearance of 6.4 cm/2.5 in. + right clearance of 6.4 cm/2.5 in.).
Table 4-4. VSM5-VTSS Cabinet Superimposed Floor Loading Example
Total Front + Rear Service Clearance (Z+Z) / 2
Total Left + Right Side Clearance (X+X) / 2
7.6 cm
(3.0 in.)
61.0 cm
(24.0 in.)
91.4 cm
(36.0 in.)
121.9 cm
(48.0 in.)
152.4 cm
(60.0 in.)
55.9 cm
(22.0 in)
443 kg/m
2
(91 lb./ft
2
)
340 k.g/m
2
(70 lb/ft
2
)
308 kg/m
2
(63 lb./ft
2
)
285 kg/m
2
(58 lb./ft
2
)
268 kg/m
2
(55 lb./ft
2
)
96.5 cm
(38.0 in)
374 kg/m
2
(77 lb./ft
2
)
295 k.g/m
2
(60 lb/ft
2
)
270 kg/m
2
(55 lb./ft
2
)
252 kg/m
2
(52 lb./ft
2
)
239 kg/m
2
(49 lb./ft
2
)
116.8 cm
(46.0 in)
350 kg/m
2
(72 lb./ft
2
)
279 kg/m
2
(57 lb./ft
2
)
257 kg/m
2
(53 lb./ft
2
)
241 kg/m
2
(49 lb./ft
2
)
229 kg/m
2
(47 lb./ft
2
)
137.2 cm
(54.0 in)
331 kg/m
2
(68 lb./ft
2
)
267 kg/m
2
(55 lb./ft
2
)
247 kg/m
2
(51 lb./ft
2
)
232 kg/m
2
(48 lb./ft
2
)
222 kg/m
2
(45 lb./ft
2
)
157.5 cm
(62.0 in)
315 kg/m
2
(64 lb./ft
2
)
256 kg/m
2
(52 lb./ft
2
)
238 kg/m
2
(49 lb./ft
2
)
225 kg/m
2
(46 lb./ft
2
)
215 kg/m
2
(44 lb./ft
2
)
Notes:
• See Figure 4-3 on page 4-53 for the location and load of each VTSS cabinet support point.
• Values assume 15 lb./ft
2
(73 kg/m
2
) superimposed dead load over entire area for raised floor, cables, etc., and
15 lb./ft
2
(73 kg/m
2
) live load for personnel and equipment in clearance areas between units.
• Loading of adjacent floor areas must be considered when evaluating overall floor capacity.
• To evaluate floor loading for other possible configurations, consult a structural engineer.