96257 Sun Confidential: Internal Only A-61
Revision A
Power Safety Grounding Diagram – Side 1
■ Power Safety Grounding Diagram – Side 1
Figure A-4. VSM5-VTSS Power Safety Grounding Diagram – Side 1
A504_068
Array PS-1
Power Strip 1
#16 Pigtail
Not a Controlled
Connection for
Safety Purposes
#16 Pigtail
#16 Pigtail
#16 Pigtail
#16 Pigtail
Array PS-3
Array PS-5
Array PS-7
Frame
Frame
Frame
Frame
6-32
6-32
6-32
6-32
3
3
3
3
6
7
6.3A(X2)
6.3A(X2)
6.3A(X2)
6.3A(X2)
9
9
#16
6-32
Frame
TBD
6-32
3X
PDU - 1
AUX-PS-1
IXP2-1
8
2A
J1
6-32
P807
#22
#16
Line Filter
#10 Studs
#12
#12
#12
#16
#16
Relay
K100
CB100
5
1
#16
#10
4
4X
6-32
2X
6-32
Frame
AC-1 to
Logic PS
AC-1 to
Array Ps’s
Mate-N-LOK
IEC320
#10
Studs
AMP CPC
Black or
Brown
Blue or
White
#10 Wire
Cable
Green/
Yellow
Russell-Stoll
3750
L N G
Single Phase
AC-1 Input Plug
J102
J101 J100
#16 Cable
6-32
Frame
3
6
Logic PS -1
7
IEC320
15A
15A
Logic Card
Cage
The frame connection to the PDU chassis
must be made to the same panel that has the
grounded stud.
The array and logic DPCS’s are safety
grounded through the input AC connector.
There may be metal-metal contact between
DCPS chassis and machine frame. Frame
which is not controlled and can not serve as
a safety ground.
On PDU chassis, there is a dedicated nut
for incoming ground wire connection to
chassis stud.
CB100 = 30 rating. TBD delay curve
Both phases are fused in logic and array PS’s.
Logic PS fuse = 3AB, 250V, 15A, standard
delay curve
Array PS fuse = 3AG, 250V, 6.3A, slow-blow
delay curve
Only one phase is fused in AUX PS.
Ground connections to IEC-320 connectors in
power strips are double crimped
#16 AWG IN 0.250 fast-on tab connectors.
Notes
1
2
3
4
5
6
7
8
9