83
-
5
15
-
0
00
Rev.
B
7
Cooling fan speed control for low noise and extended fan life.
Zero stacking
-
no ventilation holes at the top and bottom surface of the power supply.
Optional GPIB
interface (SCPI compatible).
Optional Isolated Analog programming/monitoring (0
-
5V or 0
-
10V, user selectable and 4
-
20mA).
1.2.4
Multiple output power system
The Genesys
TM
power supplies series can be configured into a programmable power system of up to
31 units
using the built
-
in RS232/RS485 communication port and the RS485 linking cable provided
with each power supply.
In a GPIB system, each power supply can be controlled using the optional GPIB controller (factory
installed).
1.2.5
Control via the serial communicati
on port
The following parameters can be programmed /
monitored
via the serial communication port:
1.
Output Voltage setting.
2.
Output Current setting.
3.
Output Voltage measurement.
4.
Output On/Off control.
5.
Output Current measurement.
6.
Foldback protection setting
7.
Ove
r
-
voltage protection setting and readback.
8.
Under
-
Voltage limit setting and readback.
9.
Power
-
supply start up mode (last setting or safe mode).
1.2.6
Analog voltage programming and monitoring
Analog inputs and outputs are provided at the rear panel for analog contr
ol of the power supply. The
Output Voltage and the Current can be programmed by analog voltage or by resistor, and can be
monitored by analog voltage. The power supply output can be remotely set to On or Off and analog
signals monitor the proper operation
of the power supply and the mode of operation (CV/CC).
1.2.7
Parallel operation
Genesys
TM
power supplies of the same Output Voltage and Current rating can be paralleled in a
master
-
slave configuration with automatic current sharing to i
n
crease power availabl
e.
1.2.8
Output connections
Output connections are made to rear panel bus
-
bars for models up to 100V and to a 4
-
terminal wire
clamp connector for models above 100V rated output voltage. Either the positive or negative terminal
may be grounded or the output may b
e floated. Models up to 60VDC Rated Output shall not float ou
t-
puts more than +/
-
60VDC above/below chassis ground. Models >60VDC Rated Output shall not float
outputs more than +/
-
600VDC above/below chassis ground. Contact factory for assistance with higher
float vol
t
age applications.
Local or remote sense may be used. In remote sense, the voltage drop on the load wires should be
minimized. Refer to the specifications for the maximum vol
t
age drop value.