TOA Electronics NX-100S Network Cables User Manual


 
4-19
Chapter 4: SYSTEM SETTINGS (SETTING USING BROWSER)
(3) Serial Port Setting
[Baud Rate]
Select [9600], [19200], [38400], [57600], or [115200]
[Data Length (bit)]
Select to [7 bits] or [8 bits].
[Parity]
Select [Even], [Odd], or [None].
[Stop Bit]
Select [1 bit] or [2 bits].
[Flow Control]
Select the type of flow control.
None: Flow control is not performed.
Xon/Xoff: Performs software flow control.
Hardware: Performs hardware flow control.
(4) Other
[Automatic Cutoff Time (minutes)]
Set the time interval (timeout duration: 0 – 60 minutes) before the connected unit is automatically
disconnected following the end of the last communication. The connected unit is not disconnected if the
timeout duration is set to [0]. This function is only available for TCP connections.
[Transmit/Receive RAW data.]
Tick the checkbox when transmitting and receiving raw data. Data with control information to be utilized
between NX-100 units is usually transmitted, but raw data communications are generally carried out
without such control information. However, when communications with other connected units are cut off,
this cannot be detected. Raw data communications are only possible while in TCP connection mode.
(5) Save button
Updates the NX-100 setting file.
Caution
Never restart the unit or turn off the power during updates, or while the STATUS indicator on the front
panel of the NX-100 is flashing.
Note
Serial bridge function data can be transmitted at every 20 ms intervals or when its data length becomes 1024
bytes within 20 ms. This serial bridge function cannot be used for the equipment that communicate with data
less than 1024 bytes long at intervals shorter than 20 ms.