TOSHIBA
25
4.3.1 Recommended Wire Size and Torque Requirements For UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
INPUT: OUTPUT:
AWG
(L1)(L2)(L3) Tightening
(H1) (H2) (H3)
NEUTRAL
AWG
AWG
NEUTRAL
AWG
Torque
208 1/0 250MCM 208/120 1/0 250MCM 200 in-lbs.
220 1/0 4/0 220/127 1/0 4/0 200 in-lbs.
240 1 N/A 240 1 N/A 200 in-lbs.
380 4 1/0 380/220 4 1/0 200 in-lbs.
400 4 1/0 400/230 4 1/0 200 in-lbs.
415 4 1 415/240 4 1 200 in-lbs.
480 6 2 480/277 6 2 200 in-lbs.
600 6 N/A 600 6 N/A 200 in-lbs.
All wire sizes are per the NEC. Maximum Wire Size for Input and Output is 1/0 AWG.
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size for Neutral
is 250MCM.
50 kVA
Input/ Output (GND)
AWG Tightening Torque
208-240VAC 6 200 in-lbs.
380-480VAC 6 200 in-lbs.
600VAC 8 200 in-lbs.
50 kVA
Battery (+) / (-)
AWG Tightening Torque
(+) (-) 250MCM 200 in-lbs.
Maximum Wire Size for Battery is 250MCM.
Minimum Wire Size and Torque requirements
UPS Optional Bypass Input Terminals TB4 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
50 kVA Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
AWG NEUTRAL AWG Tightening Torque
208/120 1/0 250MCM 200 in-lbs.
220 1/0 4/0 200 in-lbs.
240 1 N/A 200 in-lbs.
380 4 1/0 200 in-lbs.
400 4
1/0
200 in-lbs.
415 4 1 200 in-lbs.
480 6 2 200 in-lbs.
600 6 N/A 200 in-lbs.
Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM.