When the battery test is completed, the previous operation will be resumed and the
main system MONI screen will be displayed. If the battery test detects a low DC
battery voltage, then the message screen will display:
- UPS ON-LINE -
OUTPUT VOLTAGE=208V
CURRENT=38/55/48%
* LOW BATTERY *
If the battery test passes then the following screen message will be displayed:
- UPS ON-LINE -
OUTPUT VOLTAGE=208V
CURRENT=38/55/48%
DATE (DAY) TIME
If the inverter is not operating when the BATT TEST key is press then the function
will be inhibited and the following screen message will be displayed:
- BATTERY TEST -
BATTERY VOLTAGE=324V
BATT. TEST INHIBITED
NOTE:
After start-up, the battery test function is inhibited for 20-min. (only one battery test
can be done approximately every 20-min.).
5.21.7 BUZZ STOP Key
The “BUZZ STOP” key has no effect on the LCD screen display. However if the UPS
alarm buzzer is on, pressing this key will silence it. If the alarm buzzer is not on,
pressing this key has no effect.
5.21.8 RESET Key
The RESET key function is used to 'Reset' the LCD display board software should a
system lock-up occur. The reset does not reset the variables in the memory. Use of
the RESET function is very important when a fatal communication error has occurred.
Press and hold the RESET key for a period of at least five seconds to reset the
display software. The 'display board' to 'main board' interface will begin a new
communication sequence. If a communication response is not received by the
'display board' from the 'main board' within 15 seconds, a fatal time-out occurs and
the following system message displays:
- DISPLAY ERROR -
MAIN COMM. ERROR
PRESS & HOLD RESET KEY
If the 'Reset' function is successful then the display will begin from the 'Start-up
screen' and then change to the 'main monitor' screen.