Toshiba G8000 Power Supply User Manual


 
4
G8000 Series Installation and Operation Manual (380 V)
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, •
hard hats, safety glasses, face shields, ash clothing, etc., in accordance with established safety
practices.
Be trained in rendering rst aid.•
For further information on workplace safety visit www.osha.gov.
2.4 Factory Authorized Personnel
Factory authorized personnel have been factory trained and certied to install, service, and repair the
UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized
personnel nearest you.
3 Important Safety Instructions
The following contains important instructions that should be followed during the installation, operation,
and maintenance of the G8000 Series UPS.
Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or
replacing the batteries for each system. Keep unauthorized personnel from batteries. Only a certied
service representative with battery experience should perform service on batteries.
The UPS system input and output is NOT equipped with an over-current protection device, or an
output disconnection at the AC output. The user should provide circuit breakers between the UPS AC
input (or Bypass input) and the power sources and between the UPS output and the critical load input.
The minimum device ratings are listed in Table 3.1.
The maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF.
If the UPS is exposed to the same ambient temperature as the battery system, the maximum operating
ambient temperature is 86 °F (30 °C) at 1.0 PF, 90 °F (32 °C) at 0.8 PF. Table 3.2 lists the nominal battery
voltage.
CAUTION
Misuse of this equipment could result in personal injury and/or equipment damage.
In no event will Toshiba Corporation be responsible or liable for either indirect or
consequential damage or injury that may come from the use of this equipment.
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
Ca p a C i t y Ra t e d Ou t p u t in p u t BR e a k e R Ra t i n g Ou t p u t BR e a k e R Ra t i n g
120 kVA 380 V/220 V 380 V-300 A 380 V-225 A
180 kVA 380 V/220 V 380 V-450 A 380 V-350 A