Toshiba G8000 Power Supply User Manual


 
26
G8000 Series Installation and Operation Manual (380 V)
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the oor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions.
4 x 5/16 in. (16 mm)
diameter screw holes
4 screw holes
(Side View)
Anchor Bolt
FIGURE 10.2
ANCHOR BOLT INSTALLATION DETAIL
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
21 11/16 in.
(551 mm)
Back
Front
4 x 0.5 in. - Dia. (12 mm)
29 11/16 in. (754 mm)
120/180 kVA