40
G8000 Series Installation and Operation Manual (380 V)
12.2 Mechanical- Specication
Nominal Capacity 120 kW 180 kW
Cabinet Protection
Conformity
IEC298 IP20*
Exterior Paint
Sherwin Williams, HHT2-7055, 079 Beige
Texture
Panel Thickness
FRONT: 1/16 in. (1.6 mm)
BACK/SIDE/TOP: 3/64 in. (1.2 mm)
BOTTOM: 1/8 in. (3.2 mm)
Input/Output
Cabling Entrance
TOP and BOTTOM
Ground/Control
Wiring Entrance
TOP and BOTTOM
Outline Dimension
W: 55.1 in. (1400 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Unit Weight 2467 lbs (1119 kg) 2980 lbs (1352 kg)
Shipping Weight 2556 lbs (1159 kg) 3069 lbs (1392 kg)
Floor Loading Per
Footprint
3280 lbs/ft
2
(16,014 kg/m
2
)
3733 lbs/ft
2
(18,226 kg/m
2
)
Clearance
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
35,725 BTU/h
(9002 kcal/h)
53,587 BTU/h
(13,503 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.
12.3 Electrical Specication
WARNING
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained
personnel open the front cover.