Toshiba G8000 Power Supply User Manual


 
40
G8000 Series Installation and Operation Manual (380 V)
12.2 Mechanical- Specication
Nominal Capacity 120 kW 180 kW
Cabinet Protection
Conformity
IEC298 IP20*
Exterior Paint
Sherwin Williams, HHT2-7055, 079 Beige
Texture
Panel Thickness
FRONT: 1/16 in. (1.6 mm)
BACK/SIDE/TOP: 3/64 in. (1.2 mm)
BOTTOM: 1/8 in. (3.2 mm)
Input/Output
Cabling Entrance
TOP and BOTTOM
Ground/Control
Wiring Entrance
TOP and BOTTOM
Outline Dimension
W: 55.1 in. (1400 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Unit Weight 2467 lbs (1119 kg) 2980 lbs (1352 kg)
Shipping Weight 2556 lbs (1159 kg) 3069 lbs (1392 kg)
Floor Loading Per
Footprint
3280 lbs/ft
2
(16,014 kg/m
2
)
3733 lbs/ft
2
(18,226 kg/m
2
)
Clearance
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Heat Rejection
35,725 BTU/h
(9002 kcal/h)
53,587 BTU/h
(13,503 kcal/h)
*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.
12.3 Electrical Specication
WARNING
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained
personnel open the front cover.