Toshiba G8000 Power Supply User Manual


 
39
G8000 Series Installation and Operation Manual (380 V)
12 UPS Specications
12.1 General Specication
Terms
Specication Remarks
Conforming Standard UL1778-2001 UL, cUL
Ambient Temperature
PF = 1.0: 32 – 86 °F (0 – 30 °C)
PF = 0.8: 86 – 104 °F (30 – 40 °C)
Relative Humidity 30% – 90% Non-condensing
Altitude
< 3280 ft. (< 1000 m) Contact Toshiba Technical
Support for installation above
3280 ft. (1000 m)
Audible Noise 68 dB 39 in. (1m) away from front
Insulation Resistance 3 MΩ With 500V-Megger
Insulation Breakdown
AC 2 kV – 1 min. Main Circuit
AC 1.5 kV – 1 min. External Interface
AC 500 V – 1 min. Control Circuit